Electrical Safety Program
Document Type: Program
Version: 1.0
Last Updated: February 2026
Distribute To: All Employees, Electrical Trades
Purposeโ
Establish procedures to protect workers from electrical hazards including shock, electrocution, arc flash, and burns.
โ ๏ธ CRITICAL INFORMATIONโ
Electricity Killsโ
- Electrocution is among top 4 causes of construction deaths
- As little as 50mA can cause death
- Contact with power lines is often fatal
- Water greatly increases hazard
Electrical Hazardsโ
| Hazard | Description | Prevention |
|---|---|---|
| Shock | Current through body | Insulation, GFCI, proper tools |
| Electrocution | Fatal shock | All prevention methods |
| Burns | From arcing or flash | Distance, PPE, de-energize |
| Arc Flash | Explosive release | De-energize, arc-rated PPE |
| Fire | Overloading, sparks | Proper sizing, good connections |
General Electrical Safetyโ
All Workers Must:โ
- Consider all electrical equipment "live" until verified
- Never work on energized circuits (unless qualified)
- Report damaged cords, equipment, outlets
- Keep water away from electrical
- Know location of disconnects
Qualified Persons Only:โ
- Work on or near exposed energized parts
- Test for voltage
- Perform lockout/tagout
- Work within arc flash boundary
Extension Cords and Toolsโ
Extension Cord Requirements:โ
- Three-wire (grounded)
- Appropriate gauge for load
- Cord rated for intended use
- No spliced or taped cords
- Protected from damage
Inspection Before Use:โ
- No damaged insulation
- Ground pin intact
- No exposed conductors
- Strain relief intact
- Not overheated
Do NOT:โ
- Use cords as permanent wiring
- Run through doors/windows (crush hazard)
- Daisy-chain multiple cords
- Overload cord capacity
- Use indoor cords outdoors
Ground Fault Circuit Interrupters (GFCI)โ
GFCI Required For:โ
- All 120V, 15 and 20 amp receptacles
- Used by workers on construction sites
- Outdoor/wet locations
GFCI Types:โ
- Receptacle type (built-in)
- Portable/cord type
- Panel-mounted breakers
GFCI Testing:โ
- Test before each use
- Press TEST button
- Should trip immediately
- Press RESET to restore
- Do not use if fails test
Temporary Wiringโ
Requirements:โ
- Protect from damage
- Proper clearances
- Labeled as temporary
- GFCI protection
- Regular inspection
Temporary Panel:โ
- Weatherproof (outdoor)
- Properly grounded
- Breakers appropriately sized
- Access clear (3 feet)
Lockout/Tagout (LOTO)โ
When Required:โ
- Maintenance or repair work
- When unexpected startup could cause injury
- Working on electrical systems
LOTO Steps:โ
- Notify affected employees
- Identify energy sources
- Isolate equipment from energy
- Lock energy isolating device
- Tag with name and date
- Verify zero energy state
LOTO Rules:โ
- Each worker applies own lock
- Locks removed only by person who applied
- Test before working to verify de-energized
- Never remove another's lock
Working Near Power Linesโ
Minimum Approach Distances:โ
| Voltage | Distance |
|---|---|
| Up to 50kV | 10 feet |
| Over 50kV | 10 feet + 0.4"/kV over 50 |
| Unknown | Assume high voltage, 20+ feet |
Equipment Near Power Lines:โ
- Maintain safe distances
- Use spotter when operating near lines
- Lower booms when traveling
- Consider de-energization request
Contact with Power Lines:โ
IF EQUIPMENT CONTACTS LINES:
- Stay in equipment if possible
- Warn others to stay away
- Call for help
- If must exit: Jump clear, don't step out
- Shuffle/hop away (don't run)
Overhead Power Linesโ
Before Work Near Lines:โ
- Identify all overhead lines
- Determine voltage (or assume high)
- Calculate safe distance
- Install barriers/warning lines
- Use spotters
- Consider de-energization
Protection Methods:โ
- Physical barriers
- Warning lines and signs
- Insulated link sticks
- Equipment proximity alarms
Underground Utilitiesโ
Before Excavating:โ
- Call 811 (utility locate)
- Wait for marks
- Hand dig within tolerance zone
- Expose utilities carefully
- Maintain safe distances
Arc Flash Protectionโ
Arc Flash Hazards:โ
- Explosive energy release
- Extreme heat (35,000ยฐF)
- Molten metal spray
- Pressure wave
- Bright flash
Protection:โ
- De-energize when possible
- Arc-rated PPE for energized work
- Maintain safe boundaries
- Only qualified workers
Arc Flash PPE:โ
- Arc-rated face shield
- Arc-rated clothing
- Leather gloves
- Safety glasses under shield
Electrical Safety Trainingโ
All Workers:โ
- Electrical hazard recognition
- GFCI use and testing
- Damaged equipment reporting
- Emergency procedures
Qualified Electrical Workers:โ
- NFPA 70E requirements
- Arc flash hazards
- Lockout/tagout procedures
- Testing and verification
- PPE selection and use
Electrical Inspection Checklistโ
================================================================
ELECTRICAL SAFETY INSPECTION
================================================================
Date: ____________ Project: _______________________________
Inspector: ________________________________________________
================================================================
TEMPORARY POWER:
โ Pass โ Fail Panel properly grounded
โ Pass โ Fail Breakers appropriately sized
โ Pass โ Fail 3-foot clearance maintained
โ Pass โ Fail GFCI protection in use
โ Pass โ Fail Weatherproof (if outdoor)
EXTENSION CORDS:
โ Pass โ Fail Three-wire cords
โ Pass โ Fail No damaged cords
โ Pass โ Fail Ground pins intact
โ Pass โ Fail Protected from damage
โ Pass โ Fail Not overloaded
TOOLS AND EQUIPMENT:
โ Pass โ Fail Properly grounded
โ Pass โ Fail Guards in place
โ Pass โ Fail Cords in good condition
โ Pass โ Fail GFCI in use
OVERHEAD LINES:
โ Pass โ Fail โ N/A Safe distances maintained
โ Pass โ Fail โ N/A Warning signs posted
โ Pass โ Fail โ N/A Spotters used (equipment)
GENERAL:
โ Pass โ Fail No exposed wiring
โ Pass โ Fail Covers on all boxes/panels
โ Pass โ Fail No unauthorized electrical work
โ Pass โ Fail Proper clearances maintained
================================================================
Issues Found:
___________________________________________________________
___________________________________________________________
Corrective Actions:
___________________________________________________________
Signature: __________________________ Date: _______________
================================================================
Emergency Responseโ
Electrical Emergency:โ
- Do NOT touch victim if still in contact
- De-energize if possible
- Call 911
- Use non-conductive object to separate
- Begin CPR if needed and trained
- Treat for shock
Electrical Fire:โ
- Use CO2 or dry chemical extinguisher
- Never use water on electrical fire
- De-energize if possible
Related Documentsโ
- Lockout/Tagout Procedure
- Emergency Action Plan
- PPE Requirements
- JHA Procedure
OSHA Referencesโ
- 29 CFR 1926.400-449 (Electrical)
- 29 CFR 1926.405 (Wiring Methods)
- 29 CFR 1926.416 (General Requirements)
- 29 CFR 1926.417 (Lockout/Tagout)
- NFPA 70E (Electrical Safety)
Template provided by support.construction. Customize with your company information.